Filterfan PF 42500, PF 43000/ Exhaust Filter PFA 40000
Description
- Maintains a UL Tested NEMA Type 12 seal against enclosure
- UL Recognized to UL 508a, category NITW2/8, UL File #E175229
- Patented “Click & Fit” design provides a hardware free installation!
- Plastic made from strong, heat resistant (ABS-FR), UL 94 VO fire approved material
- Fan motor is CSA approved
- Options: Black grills
Part No. |
Voltage |
Power |
Mating Exhaust Filter |
Ship Wt. lbs |
PF42500T12LG |
115V |
20W |
PFA40000LG |
4.0 |
PF42500T12LG230 |
230V |
18W |
PFA40000LG |
4.0 |
PF42500T12LG24 |
24V |
5W |
PFA40000LG |
4.0 |
PF43000T12LG |
115V |
40W |
PFA40000LG |
5.0 |
PF43000T12LG230 |
230V |
39W |
PFA40000LG |
5.0 |
PF43000T12LG24 |
24V |
12W |
PFA40000LG |
5.0 |
Airflow data |
PF 42500 |
PF 43000 |
PFA 40000 |
Filter material |
NEMA Type 12 Filtermat |
NEMA Type 12 Filtermat |
NEMA Type 12 Filtermat |
Unimpeded airflow |
94 CFM |
169 CFM |
- |
Capacity free-flow |
53 W/K |
I88 W/K |
- |
Airflow in combination |
67 CFM |
142 CFM |
- |
(Filterfan + Exhaust Filter) |
(PF 42500 + PFA 40000) |
(PF 43000 + PFA 40000) |
- |
Capacity in combination |
38 W/K |
69 W/K |
- |
(Filterfan + Exhaust Filter) |
(PF 43000 + PFA 40000) |
(PF 43000 + PFA 40000) |
- |
Max. static pressure (Airflow = 0 m3/h) |
49 Pa |
112 Pa |
- |
Filtration efficiency |
91% |
91% |
91% |
Filter material grade |
G 4 (DIN EN 779) |
G 4 (DIN EN 779) |
G 4 (DIN EN 779) |
Duty cycle |
100% |
100% |
- |
Technical data |
PF 42500
AC/DC |
PF 43000
AC/DC |
PFA 40000 |
Outside dimensions in mm
(height x width x installation depth) |
252 x 252 x 97 |
252 x 252 x 113 |
252 x 252 x 38 |
Bearing type |
ball bearings |
ball bearings |
- |
Fitting position |
any, horizontal airflow preferred |
any |
Construction |
housing and guard of sprayed thermoplastic, self-extinguishing, UL 94 VO |
Weight |
1.18 kg |
1.67 kg |
0.46 kg |
Safety protection |
in accordance with DIN 31 001 |
- |
Color |
|
Connection |
cage clamp |
cage clamp |
- |
Supplementary data |
PF 42500 |
PF 43000 |
PFA 40000 |
Operating temperature |
– 15 °C (- 5 °F) to / bis + 55 °C (+ 131 °F) |
Storage temperature |
– 20 °C (- 4 °F) to / bis + 70 °C (+ 158 °F) |
Max. relative humidity |
90% |
System of protection |
NEMA Type 12, IP 55 (EN 60 529), when installed as specified |
Basic Accessories |
parts kit filter mat, user manual radiant heater, fan heater, thermostat, hygrostat |
Approvals |
UL Recognized |
* Tolerance installation cutout |
177 + 1/-0 thickness of material to 2 mm |
|
178 + 1/-0 thickness of material > 2 mm < 3 mm |
|